AFW (Affinity Water Ltd)

Report Data Range: For the whole year 2021

Table 1: Quality of water leaving service treatment works – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of works with failures

Nitrite (Total)

A013B

0.1 mg NO2/l

1,112

0

< 0.007

0.01509

0

Totals

1,112

0

Table 2: Quality of water leaving service treatment works – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of works with failures

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

13,398

0

0

0

0

Total Coliforms (Confirmed)

C001

0 number/100 ml

13,398

1

0

0

1

Totals

26,796

1

Table 3: Quality of water leaving service treatment works – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

13,398

N/A

0

4

Residual Disinfectant – Total

C010

No abnormal change

13,404

N/A

0

4

Turbidity – Indicator

A002A

1 NTU

13,400

0

<0.1

0.33

Totals

40,202

0

Table 4: Quality of water leaving service reservoirs – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of reservoirs failing standard

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

7,643

0

0

0

0

Total Coliforms (Confirmed)

C001

0 number/100 ml

7,643

5

0

0

0

Totals:

15,286

5

Table 5: Quality of water leaving service reservoirs – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

7,642

N/A

0

260

Residual Disinfectant – Total

C010

No abnormal change

7,645

N/A

0.06

0.78

Totals:

15,287

0

Table 9: Quality of water at consumer’s tap (zones) – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of zones failing standard

1 2-Dichloroethane (Total)

F001

3 µg/l

689

0

<0.09

<0.14

0

Antimony

B008A

5 µg Sb/l

677

0

<0.2

0.51522

0

Arsenic (Total)

B001A

10 µg As/l

677

0

<1

2.5698

0

Benzene (Total)

F002

1 µg/l

691

0

<0.03

<0.07

0

Benzo[a]Pyrene (Total)

D007

0.01 µg/l

700

0

<0.0018

<0.0018

0

Boron

D005A

1 mg B/l

677

0

<0.1

0.3476

0

Bromate

F003

10 µg BrO3/l

677

0

<0.3

3.522

0

Cadmium (Total)

B002

5 µg Cd/l

677

0

<0.2

<0.2

0

Chromium (Total)

B004

50 µg Cr/l

677

0

<0.5

5.031

0

Copper (Total)

A024A

2 mg Cu/l

677

0

<0.019

0.80548

0

Cyanide (Total)

B003

50 µg CN/l

678

0

<2.7

3.621

0

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

9,664

0

0

0

0

Enterococci (Confirmed)

C003

0 number/100 ml

675

0

0

0

0

Fluoride (Total)

A027

1.5 mg F/l

677

0

0.05578

0.65522

0

Lead (10 – will apply 25.12.2013)

B007B

10 µg Pb/l

677

2

<1 

6.0838

2

Mercury (Total)

B005

1 µg Hg/l 

677

0

<0.1 

<0.1

0

Nickel (Total) 

B006A 

20 µg Ni/l

677

2

<2

7.4802

2

Nitrate (Total)

A012

50 mg NO3/l

1,000

0

<3.4

43.375

0

Nitrite – Consumer’s Taps

A013A

0.5 mg NO2/l

1,000

0

<0.007

0.09596

0

Nitrite/Nitrate formula

A013C

1 mg/l

988

0

0

<0.83288

0

Pesticides (Total by Calculation)

B010

0.5 µg/l

676

0

0

0.08669

0

Pesticides 2 4-D

P020

0.1 µg/l

295

0

<0.014

<0.016

0

Pesticides Atrazine

P004

0.1 µg/l

683

0

<0.013

0.029

0

Pesticides Carbetamide 

P010

0.1 µg/l

306

0

<0.013

<0.017

0

Pesticides Clopyralid

P018

0.1 µg/l

296

0

<0.024

0.04203

0

Pesticides Desethylatrazine

P182

0.1 µg/l

686

0

<0.008

0.05939

0

Pesticides Glyphosate

P042

0.1 µg/l

293

0

<0.005

<0.025

0

Pesticides Isoproturon

P048

0.1 µg/l

17

0

<0.012

<0.016

0

Pesticides MCPP (Mecoprop)

P053

0.1 µg/l

306

0

<0.011

0.019

0

Pesticides Metaldehyde

P226

0.1 µg/l 

306

0

<0.02

0.05472

0

Pesticides Metazachlor

P203

0.1 µg/l 

299

0

<0.011 

<0.015

0

Pesticides Propyzamide

P071

0.1 µg/l

299

0

<0.019

0.043

0

Pesticides Simazine

P073

0.1 µg/l

299

0

<0.017

<0.022

0

Polycyclic Aromatic Hydrocarbons (Total by Calculation)

B011F

0.1 µg/l

690

0

0

0

0

Selenium (Total)

B009

10 µg Se/l

677

0

<1

3.0066

0

(Total by Calculation)

D009B

10 µg/l

680

0

0

2.2857

0

Trihalomethanes (Total by Calculation)

D011

100 µg/l

681

0

0.467

53.5266

0

Totals

31,028

4

Table 10: Quality of water at consumer’s tap (zones) – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 percentile (representing a minimum)

99 percentile (representing a maximum)

No. of zones failing standard

Aluminium (Total)

A021

200 µg Al/l

2,341

1

<5

71.058

1

Colour

A001

20 mg/l Pt/Co

3,369

0

<2.5

3.6

0

Iron (Total)

A022

200 µg Fe/l

2,336

1

<15

35.026

1

Manganese (Total)

A023

50 µg Mn/l

2,336

0

<1

2.5619

0

Odour

A003

0 Dilution number at 25°C

3,368

0

0

0

0

Sodium (Total)

A009

200 mg Na/l

677

0

8.0834

51.288

0

Taste (Taste Quant)

A004

0 Dilution number at 25°C

3,367

0

0

0

0

Tetrachloromethane (Total)

D008

3 µg/l

689

0

<0.11

<0.16

0

Turbidity

A002

4 NTU

3,373

0

<0.1

0.37

0

Totals

21,856

2

Table 11: Quality of water at consumer’s tap (zones) – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 percentile (representing a minimum)

99 percentile (representing a maximum)

Ammonium (Total)

A014

0.5 mg NH4/l

995

0

<0.05

0.1604

Chloride

D002A

250 mg Cl/l

767

0

19

83

(Confirmed)

C004A

0 number/100 ml

2,333

2

0

0

Coliform Bacteria (Indicator)

C001A

0 number/100 ml

9,664

15

0

0

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

3,372

N/A

0

105

Conductivity (Electrical Conductivity)

D001

2500 µS/cm at 20°C

3,373

0

480.7

784

Hydrogen ion (pH) – Indicator (Hydrogen ion) (pH)

A006

6.5 – 9.5 pH Value

3,373

0

6.9

7.7

Residual Disinfectant – Total

C010

No abnormal change

9,665

N/A

0.09

0.98

Sulphate

A007

250 mg SO4/l

767

0

<11

118.32

Total Organic Carbon

A017

No abnormal change

675

N/A

<0.4

4.1

Totals

34,984

17