VWP (Veolia Water Projects Ltd)

Report Data Range: For the whole year 2021

Table 1: Quality of water leaving service treatment works – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of works with failures

Nitrite (Total)

A013B

0.1 mg NO2/l

16

0

<0.007

<0.007

0

Totals

16

0

Table 2: Quality of water leaving service treatment works – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of works with failures

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

156

0

0

0

0

Total Coliforms (Confirmed)

C001

0 number/100 ml

156

0

0

0

0

Totals

312

0

Table 3: Quality of water leaving service treatment works – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

156

N/A

0

5

Residual Disinfectant – Total

C010

No abnormal change

156

N/A

0.5757

0.8329

Turbidity – Indicator

A002A

1 NTU

155

0

<0.1

0.34

Totals

467

0

Table 4: Quality of water leaving service reservoirs – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of reservoirs failing standard

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

312

0

0

0

0

Total Coliforms (Confirmed)

C001

0 number/100 ml

312

0

0

0

0

Totals:

624

0

Table 5: Quality of water leaving service reservoirs – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

312

N/A

0

18

Residual Disinfectant – Total

C010

No abnormal change

312

N/A

0.4013

0.69

Totals:

624

0

Table 8: Quality of water leaving bulk supply points – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 percentile (representing a minimum)

99 percentile (representing a maximum)

Gross Alpha

F004

0.1 Bq/l

16

0

<0.018

<0.034

Gross Beta

F005

1 Bq/l

16

0

<0.016

0.045

Tritium

F006

100 Bq/l

16

0

<5

7.2

Totals

48

0

Table 9: Quality of water at consumer’s tap (zones) – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of zones failing standard

1 2-Dichloroethane (Total)

F001

3 µg/l

6

0

<0.09

<0.14

0

Antimony

B008A

5 µg Sb/l

9

0

<0.2

<0.2

0

Arsenic (Total)

B001A

10 µg As/l

9

0

<1

<1

0

Benzene (Total)

F002

1 µg/l

6

0

<0.03

<0.07

0

Benzo[a]Pyrene (Total)

D007

0.01 µg/l

8

0

<0.0018

<0.0018

0

Boron

D005A

1 mg B/l

9

0

<0.1

<0.1

0

Bromate

F003

10 µg BrO3/l

8

0

<0.3

<0.3

0

Cadmium (Total)

B002

5 µg Cd/l

9

0

<0.2

<0.2

0

Chromium (Total)

B004

50 µg Cr/l

9

0

<0.5

<0.5

0

Copper (Total)

A024A

2 mg Cu/l

8

0

<0.019

0.047

0

Cyanide (Total)

B003

50 µg CN/l

8

0

<2.7

<2.7

0

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

36

0

0

0

0

Enterococci (Confirmed)

C003

0 number/100 ml

8

0

0

0

0

Fluoride (Total)

A027

1.5 mg F/l

8

0

0.045

0.062

0

Lead (10 – will apply 25.12.2013)

B007B

10 µg Pb/l

8

0

<1

<1

0

Mercury (Total)

B005

1 µg Hg/l 

9

0

<0.1

<0.1

0

Nickel (Total) 

B006A 

20 µg Ni/l

8

0

<2

<2

0

Nitrate (Total)

A012

50 mg NO3/l

8

0

15.3

30.6

0

Nitrite – Consumer’s Taps

A013A

0.5 mg NO2/l

8

0

<0.007

<0.007

0

Nitrite/Nitrate formula

A013C

1 mg/l

8

0

<0.306

<0.612

0

Pesticides (Total by Calculation)

B010

0.5 µg/l

8

0

0

0.026

0

Pesticides Atrazine

P004

0.1 µg/l

8

0

<0.013

<0.016

0

Pesticides Desethylatrazine

P182

0.1 µg/l

8

0

<0.008

<0.015

0

Polycyclic Aromatic Hydrocarbons (Total by Calculation)

B011F

0.1 µg/l

8

0

0

0.0083

0

Selenium (Total)

B009

10 µg Se/l

9

0

<1

<1

0

Trichloroethene & Tetrachloroethene – Sum Of 2 Substances (Total by Calculation)

D009B

10 µg/l

6

0

0

0.1

0

Trihalomethanes (Total by Calculation)

D011

100 µg/l

6

0

3.78

8.8

0

Totals

243

0

Table 10: Quality of water at consumer’s tap (zones) – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 percentile (representing a minimum)

99 percentile (representing a maximum)

No. of zones failing standard

Aluminium (Total)

A021

200 µg Al/l

9

0

<5

<5

0

Colour

A001

20 mg/l Pt/Co

24

0

<2.5

<2.5

0

Iron (Total)

A022

200 µg Fe/l

9

0

<15

<15

0

Manganese (Total)

A023

50 µg Mn/l

9

0

<1

<1

0

Odour

A003

0 Dilution number at 25°C

24

0

0

0

0

Sodium (Total)

A009

200 mg Na/l

9

0

5.66

10

0

Taste (Taste Quant)

A004

0 Dilution number at 25°C

24

0

0

0

0

Tetrachloromethane (Total)

D008

3 µg/l

6

0

<0.11

<0.16

0

Turbidity

A002

4 NTU

24

0

<0.1

0.27

0

Totals

138

0

Table 11: Quality of water at consumer’s tap (zones) – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 percentile (representing a minimum)

99 percentile (representing a maximum)

Ammonium (Total)

A014

0.5 mg NH4/l

8

0

<0.05

<0.05

Chloride

D002A

250 mg Cl/l

8

0

13

22

Clostridum Perfringens (Sulphite-reducing Clostridia) (Confirmed)

C004A

0 number/100 ml

8

0

0

0

Coliform Bacteria (Indicator)

C001A

0 number/100 ml

36

0

0

0

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

24

N/A

0

10

Conductivity (Electrical Conductivity)

D001

2500 µS/cm at 20°C

24

0

386

548

Gross Alpha

F004

0.1 Bq/l

14

0

<0.018

<0.034

Gross Beta

F005

1 Bq/l

14

0

<0.016

0.045

Hydrogen ion (pH) – Indicator (Hydrogen ion) (pH)

A006

6.5 – 9.5 pH Value

24

0

7.1

7.5

Residual Disinfectant – Total

C010

No abnormal change

36

N/A

0.32

0.57

Sulphate

A007

250 mg SO4/l

8

0

<11

19

Total Organic Carbon

A017

No abnormal change

7

N/A

0.5

0.7

Tritium

F006

100 Bq/l

14

0

<5

<5

Totals

225

0

Back to top