WSX (Wessex Water Services Ltd)

Report Data Range: For the whole year 2021

Table 1: Quality of water leaving service treatment works – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of works with failures

Nitrite (Total)

A013B

0.1 mg NO2/l

441

0

<0.01

<0.01

0

Totals

441

0

Table 2: Quality of water leaving service treatment works – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of works with failures

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

8,559

0

0

0

0

Total Coliforms (Confirmed)

C001

0 number/100 ml

8,559

0

0

0

0

Totals

17,118

0

Table 3: Quality of water leaving service treatment works – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

8,554

N/A

0

89

Residual Disinfectant – Free

C009

No abnormal change

8,590

N/A

0.29

0.9

Residual Disinfectant – Total

C010

No abnormal change

8,592

N/A

0.34

0.98

Turbidity – Indicator

A002A

1 NTU

8,559

0

<0.083

0.22

Totals

34,295

0

Table 4: Quality of water leaving service reservoirs – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of reservoirs failing standard

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

16,204

1

0

0

1

Total Coliforms (Confirmed)

C001

0 number/100 ml

16,204

4

0

0

0

Totals:

32,408

5

Table 5: Quality of water leaving service reservoirs – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

16,192

N/A

0

>300

Residual Disinfectant – Free

C009

No abnormal change

16,204

N/A

0.13

0.62

Residual Disinfectant – Total

C010

No abnormal change

16,203

N/A

0.19

0.69

Totals:

48,599

0

Table 6: Quality of water leaving bulk supply points – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of supply point with failures

Bromate

F003

10 µg BrO3/l

339

0

<0.4

0.8

0

Totals

339

0

Table 8: Quality of water leaving bulk supply points – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 percentile (representing a minimum)

99 percentile (representing a maximum)

Clostridum Perfringens (Sulphite-reducing Clostridia) (Confirmed)

C004A

0 number/100 ml

441

0

0

0

Totals

441

0

Table 9: Quality of water at consumer’s tap (zones) – European Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 Percentile (representing a minimum)

99 Percentile (representing a maximum)

No. of zones failing standard

1 2-Dichloroethane (Total)

F001

3 µg/l

488

0

<0.4

<0.4

0

Antimony

B008A

5 µg Sb/l

500

0

<0.2

0.2

0

Arsenic (Total)

B001A

10 µg As/l

500

0

<0.2

0.7

0

Benzene (Total)

F002

1 µg/l

488

0

<0.3

<0.3

0

Benzo[a]Pyrene (Total)

D007

0.01 µg/l

484

0

<0.0005

<0.001215

0

Boron

D005A

1 mg B/l

500

0

<0.03

0.09

0

Bromate

F003

10 µg BrO3/l

144

0

<0.4

3.855

0

Cadmium (Total)

B002

5 µg Cd/l

498

0

<0.1

<0.1

0

Chromium (Total)

B004

50 µg Cr/l

500

0

<1

<1

0

Copper (Total)

A024A

2 mg Cu/l

498

0

<0.01

0.7623

0

Cyanide (Total)

B003

50 µg CN/l

490

0

<1.2

<9

0

E coli (faecal coliforms Confirmed)

C002

0 number/100 ml

3,705

0

0

0

0

Enterococci (Confirmed)

C003

0 number/100 ml

498

0

0

0

0

Fluoride (Total)

A027

1.5 mg F/l

494

0

<0.138

0.651

0

Lead (10 – will apply 25.12.2013)

B007B

10 µg Pb/l

498

2

<0.1

4.816

2

Mercury (Total)

B005

1 µg Hg/l 

495

0

<0.05

<0.05

0

Nickel (Total) 

B006A 

20 µg Ni/l

498

2

<3

5.01

2

Nitrate (Total)

A012

50 mg NO3/l

590

0

<1.63718

41.8184

0

Nitrite – Consumer’s Taps

A013A

0.5 mg NO2/l

584

0

<0.01

<0.01

0

Pesticides (Total by Calculation)

B010

0.5 µg/l

107

0

0

0.01176

0

Pesticides Aldrin

P002

0.03 µg/l

480

0

<0.005

<0.008

0

Pesticides Atrazine

P004

0.1 µg/l

16

0

<0.009

<0.009

0

Pesticides Bentazone

P006

0.1 µg/l

16

0

<0.003

0.008

0

Pesticides Clopyralid

P018

0.1 µg/l

8

0

<0.027

<0.027

0

Pesticides Dieldrin

P028

0.03 µg/l

475

0

<0.005

<0.009

0

Pesticides Heptachlor

P043

0.03 µg/l

480

0

<0.004

<0.006

0

Pesticides Heptachlor Epoxide – Total (Trans, CIS) (Heptachlor Epoxide)

P044

0.03 µg/l

480

0

<0.011

<0.014

0

Pesticides MCPP (Mecoprop)

P053

0.1 µg/l

12

0

<0.006

<0.006

0

Pesticides Metaldehyde

P226

0.1 µg/l 

46

0

<0.01

<0.01

0

Pesticides Metazachlor

P203

0.1 µg/l 

8

0

<0.01

<0.01

0

Polycyclic Aromatic Hydrocarbons (Total by Calculation)

B011F

0.1 µg/l

457

0

0

0.00551

0

Selenium (Total)

B009

10 µg Se/l

495

0

<0.5

1.204

0

Trichloroethene & Tetrachloroethene – Sum Of 2 Substances (Total by Calculation)

D009B

10 µg/l

492

0

<0.5

<0.5

0

Trihalomethanes (Total by Calculation)

D011

100 µg/l

492

0

2.8465

42.8961

0

Totals

16,516

4

Table 10: Quality of water at consumer’s tap (zones) – National Standards

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests Failed

1 percentile (representing a minimum)

99 percentile (representing a maximum)

No. of zones failing standard

Aluminium (Total)

A021

200 µg Al/l

1,382

0

<10

20

0

Colour

A001

20 mg/l Pt/Co

1,527

0

<0.6

<2.9

0

Iron (Total)

A022

200 µg Fe/l

1,382

1

<20

50

1

Manganese (Total)

A023

50 µg Mn/l

1,382

0

<1

5

0

Odour

A003

0 Dilution number at 25°C

1,438

0

0

0

0

Sodium (Total)

A009

200 mg Na/l

499

0

5.8

52

0

Taste (Taste Quant)

A004

0 Dilution number at 25°C

1,419

3

0

0

3

Tetrachloromethane (Total)

D008

3 µg/l

492

0

<0.23

0.2784

0

Turbidity

A002

4 NTU

1,529

0

<0.083

0.237

0

Totals

11,050

4

Table 11: Quality of water at consumer’s tap (zones) – Additional Monitoring Requirements

Parameter Name

Parameter Code

Prescribed Concentration or Value

Total Number of Tests

Tests exceeding specification

1 percentile (representing a minimum)

99 percentile (representing a maximum)

Ammonium (Total)

A014

0.5 mg NH4/l

584

0

<0.026924

0.0385

Chloride

D002A

250 mg Cl/l

500

0

12

50.97

Clostridum Perfringens (Sulphite-reducing Clostridia) (Confirmed)

C004A

0 number/100 ml

54

0

0

0

Coliform Bacteria (Indicator)

C001A

0 number/100 ml

3,705

2

0

0

Colony Counts After 3 Days At 22øc (Colony Counts)

C007

No abnormal change

1,525

N/A

0

64

Conductivity (Electrical Conductivity)

D001

2500 µS/cm at 20°C

1,529

0

112.158

699.178

Hydrogen ion (pH) – Indicator (Hydrogen ion) (pH)

A006

6.5 – 9.5 pH Value

1,529

0

7.2

8.2

Residual Disinfectant – Free

C009

No abnormal change

3,725

N/A

0.07

0.61

Residual Disinfectant – Total

C010

No abnormal change

3,725

N/A

0.14

0.67

Sulphate

A007

250 mg SO4/l

500

0

11

104.96

Total Organic Carbon

A017

No abnormal change

495

N/A

<0.45

2.7

Totals

17,871

2

Back to top